Power Sharing Method Based on Droop Control for Three-Phase UPS Systems

Mohamed M. Ramadan, Magdy A. Koutb

Abstract


The main objective of this paper is to improve the power sharing capability and to achieve synchronization between three-phase Uninterruptible power supply (UPS) units in the presence of load interruption. This paper presents a droop-controlled scheme in such a way that the computation of the instantaneous value of the active power and the reactive power are taken as feedback signals to the frequency and voltage restoration control system. The restored frequency and voltage are introduced to voltage controller circuit, which produces a suitable control signal to sinusoidal pulse width modulation circuit (SPWM). Thus producing a suitable trigger pulses to the inverter gate in order to guarantee synchronization between three-phase UPS units. Simulation of two UPS units with the same ratings (4 KW) are carried out using MATLAB. The results show the effectiveness of the proposed control system in achieving synchronization and improving the power sharing capability in the presence of load interruption.

Keywords: Uninterruptible power supply; power sharing; parallel operation; droop control.

DOI: 10.7176/JETP/9-4-02

Publication date: April 30th 2019


Full Text: PDF
Download the IISTE publication guideline!

To list your conference here. Please contact the administrator of this platform.

Paper submission email: JETP@iiste.org

ISSN (Paper)2224-3232 ISSN (Online)2225-0573

Please add our address "contact@iiste.org" into your email contact list.

This journal follows ISO 9001 management standard and licensed under a Creative Commons Attribution 3.0 License.

Copyright © www.iiste.org